HVAC Applications QC-1

QC-1 More Info QC-35 More Info QC Equivalents

QC-1 Freezing Point Adjustment

chemical.net HVAC heat transfer fluids

The following formula is a guide to the amount of solution to drain and the number of gallons of QC-1 to add to a system to change the freezing point.

Formula:
QC-1 Industrial Coolant Required
 = System capacity X (desired % concentration - present % concentration)
100% - present percent concentration

For Instance: If the system capacity is 1,000 gallons and the resent concentration is 30%, and the desired concentration is 50%, then substituting these numbers into the above formula, we have:
QC-1 Industrial Coolant Required
=1,000 (50-30) =20,000 = 286 Gallons
      100 - 30              70

 

This is also the amount of solution that must be removed from the system to accommodate the QC-1 concentration

As always, if you have any questions about the above, please feel free to call Chemical.net at 888- 243-6425



 

 
 
 
Dowtherm News and Information


Chemical.net introduces an exciting new Heat Transfer Fluid: QC Eco-Green Heat Transfer Fluid. Read more Here

Chemical.net has always specialized in the ability to supply our customers with any size container they require; from small containers, to pails, and from drums to tankers. Call our friendly staff for a free quote:
888-243-6425
215-332-4000
www.chemical.net

Click here to go to Greenleaf Environmental

Click Here to go to QCLubricants

 

Home  |  About Us  |  Contact Us